Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 31, 2021, 10:10 AM
  • E 0209_01 0053A_03312021_032140.mp4

Date
03/31/2021
W/O
886006
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00209
PipeID
P02146
Time
3:10 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8715
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_886006_TV01254_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
01 0053A
Downstream MH
E 0209
Dir. of Survey
Upstream
Length Surveyed
156.9 ft.
Total Length
156.9 ft.
Structural Index
3
Structural Quick
3E00
Structural Rating
90
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
90
Pipe schematic from manhole 01 0053A to E 0209
MH: 01 0053AMH: E 0209upstream0 ft. AMH - Upstream Manhole, Survey Ends - E 02090.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish88.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"91.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"139.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"142.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"152.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start156.9 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK156.9 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK156.9 ft. MWM - Water Mark, 5 %of cross sectional area156.9 ft. MWL - Water Level, 5 %of cross sectional area156.9 ft. AMH - Downstream Manhole, Survey Begins - 01 0053A

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
14.8TFC
0MGOCONNECTION AT THE MH 3 OC'LOCK
156.3CM
17.5TFC
0MGOCONNECTION AT THE MH 9 OC'LOCK
65.7TFC
0MWM
0MWL
156.9AMHE 0209
0AMH01 0053A
68.3TFC
4.2CM

Properties (7)

additional_info
630074033021207
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-03-31T03:10:32-07:00
documentation
PROPIPE
is_lateral_inspection
false