Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 8, 2021, 11:03 AM
  • 01 0093_01 0092_04082021_041733.mp4

Date
04/08/2021
W/O
886006
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00209
PipeID
P00762
Time
4:03 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8724
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
06
Purpose
Routine Assessment
Project
RFIR_WO_886006_TV01254_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
01 0093
Downstream MH
01 0092
Dir. of Survey
Downstream
Length Surveyed
332.5 ft.
Total Length
332.5 ft.
Structural Index
3
Structural Quick
4C3L
Structural Rating
278
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
3
Overall Quick
Overall Rating
279
Pipe schematic from manhole 01 0093 to 01 0092
MH: 01 0093MH: 01 0092downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - 01 00933.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start25 ft. FM - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES90 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"112.2 ft. FS - Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES140.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"195.2 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES, Start209 ft. RFL - Roots Fine Lateral, at 02 o'clock209 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"259.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"289 ft. FM - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES, Finish330.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish332.4 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK332.5 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK332.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0092

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    25 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES

    112.2 ft. - Fracture Spiral, from 07 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

    195.2 ft. - Fracture Multiple, from 11 to 01 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
25FM
209RFL
259.7TFC
289FM
209TF
0MWM
90TFC
332.5MGOCONNECTION AT THE MH 3 OC'LOCK
0MGOCONNECTION AT THE MH 9 OC'LOCK
0MWL
332.4MGOCONNECTION AT THE MH 9 OC'LOCK
140.9TF
0MGOCONNECTION AT THE MH 3 OC'LOCK
112.2FS
330.1CM
332.5AMH01 0092
3.1CM
195.2FM
0AMH01 0093

Properties (7)

additional_info
630074040721204
custom_field_three
MULTIPLE CRACKS/FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-04-08T04:03:15-07:00
documentation
PROPIPE
is_lateral_inspection
false