Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 8, 2021, 09:52 AM
  • 01 0062_01 0061_04082021_031007.mp4

Date
04/08/2021
W/O
886006
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00209
PipeID
P00731
Time
2:52 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8724
Sewer Name
01 HOOPER AVENUE-COMPTON CREEK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_886006_TV01254_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
01 0062
Downstream MH
01 0061
Dir. of Survey
Downstream
Length Surveyed
355.5 ft.
Total Length
355.5 ft.
Structural Index
3
Structural Quick
423M
Structural Rating
218
O&M Index
1
O&M Quick
4532
O&M Rating
83
Overall Index
2
Overall Quick
Overall Rating
301
Pipe schematic from manhole 01 0062 to 01 0061
MH: 01 0062MH: 01 0061downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 00623.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start29.7 ft. RML - Roots Medium Lateral, at 02 o'clock, 15 %, within 8 inches of joint: NO29.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"31.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"35.6 ft. FM - Fracture Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES70.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"70.8 ft. RML - Roots Medium Lateral, at 02 o'clock, 35 %, within 8 inches of joint: NO73.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"73.7 ft. RBL - Roots Ball Lateral, at 10 o'clock, 75 %76.8 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start107.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"107.5 ft. RBL - Roots Ball Lateral, at 02 o'clock, 75 %114.7 ft. RFC - Roots Fine Connection, at 10 o'clock115.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"127.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"147.5 ft. FM - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES149.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"149.5 ft. RBL - Roots Ball Lateral, at 02 o'clock, 90 %163.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"163.6 ft. RBL - Roots Ball Lateral, at 02 o'clock, 85 %190.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"205.6 ft. RBL - Roots Ball Lateral, at 10 o'clock, 75 %205.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"229.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"274.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"277.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"319.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"322 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"354.9 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish354.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish354.9 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK CAPPED355.5 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK355.5 ft. AMH - Downstream Manhole, Survey Ends - 01 0061

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

    35.6 ft. - Fracture Multiple, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    76.8 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    147.5 ft. - Fracture Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

Observations (36)

DistanceCodeObservation
355.5MGOCONNECTION AT THE MH 3 OC'LOCK
205.6RBL
29.7RML
229.3TF
73.7TF
114.7RFC
190.7TF
277.2TF
3.1CM
70.8TF
31.4TF
163.6TF
29.7TF
354.9RFJ
205.6TF
127.8TF
70.8RML
163.6RBL
73.7RBL
354.9CM
354.9MGOCONNECTION AT THE MH 9 OC'LOCK CAPPED
274.6TF
322TF
115.8TF
355.5AMH01 0061
0MWM
35.6FM
107.5TF
0MWL
147.5FM
76.8RFJ
149.5TF
0AMH01 0062
319.4TF
107.5RBL
149.5RBL

Properties (7)

additional_info
630074040721204
custom_field_three
MULTIPLE CRACKS/ SOME FRACTURE'S
custom_field_two
3
customer
1
datetime
2021-04-08T02:52:51-07:00
documentation
PROPIPE
is_lateral_inspection
false