Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2021, 09:23 AM
  • 01 1119_01 1118_03172021_023812.mp4

Date
03/17/2021
W/O
880430
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00210
PipeID
P01970
Time
2:23 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8751
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_880430_TV01247_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
01 1119
Downstream MH
01 1118
Dir. of Survey
Downstream
Length Surveyed
275.2 ft.
Total Length
275.2 ft.
Structural Index
3
Structural Quick
3J2J
Structural Rating
270
O&M Index
2
O&M Quick
322J
O&M Rating
121
Overall Index
2
Overall Quick
Overall Rating
391
Pipe schematic from manhole 01 1119 to 01 1118
MH: 01 1119MH: 01 1118downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 11192 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start36.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"44.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"96.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 4", 6"99.6 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 6"101.9 ft. RFL - Roots Fine Lateral, from 01 to 04 o'clock - 45% GREASE101.9 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - 45% GREASE-LATERAL/ACTIVE155.4 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - 65% ROOTS-LATERAL/ACTIVE155.4 ft. RML - Roots Medium Lateral, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES163.3 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - 65% GREASE-ROOTS/LATERAL/ACTIVE163.3 ft. RML - Roots Medium Lateral, from 07 to 11 o'clock, 15 %, within 8 inches of joint: YES193.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN201.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN259.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"269.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN272.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish272.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish273 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish275.2 ft. MGO - General Observation - ROACHES @ MH275.2 ft. AMH - Downstream Manhole, Survey Ends - 01 1118

Observation photos (7)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Roots Fine Lateral, from 01 to 04 o'clock - 45% GREASE

    101.9 ft. - Roots Fine Lateral, from 01 to 04 o'clock - 45% GREASE

  • Roots Medium Lateral, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES

    155.4 ft. - Roots Medium Lateral, from 01 to 05 o'clock, 15 %, within 8 inches of joint: YES

  • Roots Medium Lateral, from 07 to 11 o'clock, 15 %, within 8 inches of joint: YES

    163.3 ft. - Roots Medium Lateral, from 07 to 11 o'clock, 15 %, within 8 inches of joint: YES

  • General Observation - ROACHES @ MH

    275.2 ft. - General Observation - ROACHES @ MH

Observations (26)

DistanceCodeObservation
0MWM
0MGOROACHES @ MH
201.2TFOPEN
272.8CM
2CM
193.6TFOPEN
155.4TFD65% ROOTS-LATERAL/ACTIVE
269.7TFOPEN
44.3TFA
2SSS
155.4RML
0MWL
101.9RFL45% GREASE
275.2MGOROACHES @ MH
99.6TBA
163.3TFD65% GREASE-ROOTS/LATERAL/ACTIVE
272.8DAGS
101.9TFD45% GREASE-LATERAL/ACTIVE
2DAGS
163.3RML
275.2AMH01 1118
259.5TFA
0AMH01 1119
36.7TFA
96.9TFC
273SSS

Properties (7)

additional_info
630069031621201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-03-17T02:23:35-07:00
documentation
PRO PIPE
is_lateral_inspection
false