Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2021, 09:38 AM
  • 01 1118_01 1117_03172021_025257.mp4

Date
03/17/2021
W/O
880430
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00210
PipeID
P01969
Time
2:38 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8751
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_880430_TV01247_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
24 in.
Upstream MH
01 1118
Downstream MH
01 1117
Dir. of Survey
Downstream
Length Surveyed
275.2 ft.
Total Length
275.2 ft.
Structural Index
3
Structural Quick
3J2J
Structural Rating
273
O&M Index
2
O&M Quick
2J11
O&M Rating
111
Overall Index
2
Overall Quick
Overall Rating
384
Pipe schematic from manhole 01 1118 to 01 1117
MH: 01 1118MH: 01 1117downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 11180 ft. MGO - General Observation - ROACHES @ MH0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"6 ft. RFL - Roots Fine Lateral, from 07 to 11 o'clock48.6 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"54 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"99.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"122.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"135.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN160.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN173.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"174.9 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: YES, 6"229.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"273 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish275.2 ft. MGO - General Observation - ROACHES @ MH275.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish275.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish275.2 ft. TFA - Tap Factory Made Active, at 06 o'clock, -, within 8 inches of joint: YES, 10" - DROP CONNECTION275.2 ft. AOC - Drop Connection, Survey Ends - 01 1117

Observation photos (4)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Roots Fine Lateral, from 07 to 11 o'clock

    6 ft. - Roots Fine Lateral, from 07 to 11 o'clock

Observations (24)

DistanceCodeObservation
0AMH01 1118
275.2MGOROACHES @ MH
273SSS
99.3TFA
0MGOROACHES @ MH
6TFA
229.5TFC
275.2DAGS
54TFA
0MWM
275.2CM
275.2TFADROP CONNECTION
122.1TFA
6RFL
174.9TBA
2CM
173.2TFC
275.2AOC01 1117
135.4TFOPEN
160.6TFOPEN
48.6TFA
2DAGS
2SSS
0MWL

Properties (7)

additional_info
630069031621201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-03-17T02:38:34-07:00
documentation
PRO PIPE
is_lateral_inspection
false