Wastewater/Activity/PacpInspection/1.0Mar 18, 2021, 08:52 AM
  • 01 1106_01 1105_03182021_020739.mp4

Date
03/18/2021
W/O
880430
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00210
PipeID
P01956
Time
1:52 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8752
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTINGTON PARK
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
07
Purpose
Routine Assessment
Project
RFIR_WO_880430_TV01247_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
24 in.
Upstream MH
01 1106
Downstream MH
01 1105
Dir. of Survey
Downstream
Length Surveyed
309.5 ft.
Total Length
309.5 ft.
Structural Index
3
Structural Quick
3K2K
Structural Rating
305
O&M Index
2
O&M Quick
412V
O&M Rating
234
Overall Index
2
Overall Quick
Overall Rating
539
Pipe schematic from manhole 01 1106 to 01 1105
MH: 01 1106MH: 01 1105downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 11060 ft. MWM - Water Mark, 30 %of cross sectional area2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start18.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN37.3 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start - DEBRIS65.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"112.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN143.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN208.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN257.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN291.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"307 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish307.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish307.2 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish307.2 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE307.2 ft. DSZ - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish309.5 ft. AMH - Downstream Manhole, Survey Ends - 01 1105

Observation photos (2)

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

Observations (20)

DistanceCodeObservation
291.3TF
307.2DAGS
307.2CM
65.1TFA
18.3TFOPEN
307.2MGOCONN @ MH 9 O'CLOCK/ACTIVE
208.3TFOPEN
143.6TFOPEN
2CM
0MWL
307.2DSZ
112.5TFOPEN
37.3DSZDEBRIS
2SSS
0AMH01 1106
0MWM
307SSS
309.5AMH01 1105
2DAGS
257.5TFOPEN

Properties (7)

additional_info
630069031721201
custom_field_three
MULTIPLE CRACKS/DEBRIS
custom_field_two
3
customer
1
datetime
2021-03-18T01:52:16-07:00
documentation
PRO PIPE
is_lateral_inspection
false