Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 19, 2021, 06:43 AM
  • 01 1094_01 1093_03182021_235659.mp4

Date
03/18/2021
W/O
880430
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00210
PipeID
P01943
Time
11:43 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8754
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_880430_TV01247_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
24 in.
Upstream MH
01 1094
Downstream MH
01 1093
Dir. of Survey
Downstream
Length Surveyed
395.1 ft.
Total Length
395.1 ft.
Structural Index
3
Structural Quick
3^2O
Structural Rating
630
O&M Index
2
O&M Quick
2O00
O&M Rating
156
Overall Index
3
Overall Quick
Overall Rating
786
Pipe schematic from manhole 01 1094 to 01 1093
MH: 01 1094MH: 01 1093downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. AMH - Upstream Manhole, Survey Begins - 01 10940 ft. MWL - Water Level, 15 %of cross sectional area2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start180.7 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES219.7 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES371.6 ft. CS - Crack Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES392.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish393 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish393 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish393 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish395.1 ft. AMH - Downstream Manhole, Survey Ends - 01 1093395.1 ft. MGO - General Observation - ROACHES @ MH395.1 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/

Observation photos (6)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    180.7 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    219.7 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES

    371.6 ft. - Crack Spiral, from 10 to 12 o'clock, within 8 inches of joint: YES

  • General Observation - ROACHES @ MH

    395.1 ft. - General Observation - ROACHES @ MH

Observations (18)

DistanceCodeObservation
0MWM
0MGOROACHES @ MH
393CM
219.7CL
0AMH01 1094
0MWL
395.1AMH01 1093
395.1MGOROACHES @ MH
393SSS
395.1MGOCONN @ MH 3 O'CLOCK/
2CM
393CM
2SSS
2CM
180.7CL
2DAGS
392.9DAGS
371.6CS

Properties (7)

additional_info
630069031821201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-03-18T23:43:30-07:00
documentation
PRO PIPE
is_lateral_inspection
false