Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 19, 2021, 07:58 AM
  • 01 1092_01 1091_03192021_011224.mp4

Date
03/19/2021
W/O
880430
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00210
PipeID
P01941
Time
12:58 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8754
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
08
Purpose
Routine Assessment
Project
RFIR_WO_880430_TV01247_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
24 in.
Upstream MH
01 1091
Downstream MH
01 1092
Dir. of Survey
Upstream
Length Surveyed
432.8 ft.
Total Length
432.8 ft.
Structural Index
3
Structural Quick
3P2P
Structural Rating
430
O&M Index
2
O&M Quick
2P00
O&M Rating
172
Overall Index
2
Overall Quick
Overall Rating
602
Pipe schematic from manhole 01 1091 to 01 1092
MH: 01 1091MH: 01 1092upstream0 ft. AMH - Upstream Manhole, Survey Ends - 01 10920 ft. MGO - General Observation - CONN @ MH 10 O'CLOCK/ACTIVE0 ft. MGO - General Observation - ROACHES @ MH2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish430.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start430.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start430.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start432.8 ft. MWM - Water Mark, 20 %of cross sectional area432.8 ft. MGO - General Observation - ROACHES @ MH432.8 ft. MWL - Water Level, 15 %of cross sectional area432.8 ft. MGO - General Observation - CONN @ MH 10 O'CLOCK/ACTIVE432.8 ft. AMH - Downstream Manhole, Survey Begins - 01 1091

Observation photos (3)

  • General Observation - ROACHES @ MH

    0 ft. - General Observation - ROACHES @ MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (14)

DistanceCodeObservation
2DAGS
0MWM
2CM
430.5DAGS
430SSS
0MGOROACHES @ MH
430.5CM
2SSS
0MWL
432.8AMH01 1092
432.8MGOCONN @ MH 10 O'CLOCK/ACTIVE
0MGOCONN @ MH 10 O'CLOCK/ACTIVE
0AMH01 1091
432.8MGOROACHES @ MH

Properties (7)

additional_info
630069031821201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-03-19T00:58:48-07:00
documentation
PRO PIPE
is_lateral_inspection
false