Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 18, 2021, 06:49 AM
  • 01 1146_01 1145_03182021_000043.mp4

Date
03/17/2021
W/O
880430
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00210
PipeID
P01997
Time
11:49 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8752
Sewer Name
01 HUNTINGTON PARK TRUNK
City
HUNTINGTON PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
04
Purpose
Routine Assessment
Project
RFIR_WO_880430_TV01247_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
01 1145
Downstream MH
01 1146
Dir. of Survey
Upstream
Length Surveyed
165.3 ft.
Total Length
165.3 ft.
Structural Index
2
Structural Quick
372F
Structural Rating
87
O&M Index
2
O&M Quick
2E00
O&M Rating
64
Overall Index
2
Overall Quick
Overall Rating
151
Pipe schematic from manhole 01 1145 to 01 1146
MH: 01 1145MH: 01 1146upstream0 ft. AMH - Upstream Manhole, Survey Ends - 01 11460 ft. MGO - General Observation - CONN @ MH 12 O'CLOCK/OPEN2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish2.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish35.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start37.9 ft. CL - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES39.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN66.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN93.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN117 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN163.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start163.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start165.3 ft. AMH - Downstream Manhole, Survey Begins - 01 1145165.3 ft. MGO - General Observation - ROACHES @ MH165.3 ft. MWL - Water Level, 15 %of cross sectional area165.3 ft. MWM - Water Mark, 20 %of cross sectional area165.3 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/UNKNOWN

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

    127.4 ft. - Crack Longitudinal, at 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    129.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
0AMH01 1145
165.3AMH01 1146
125.5TFAOPEN
48.3TFOPEN
163DAGS
129.9CM
71.4TFOPEN
0MGOROACHES @ MH
0MWL
163CM
127.4CL
2SSS
99.2TFOPEN
0MWM
0MGOCONN @ MH 9 O'CLOCK/UNKNOWN
165.3MGOCONN @ MH 12 O'CLOCK/OPEN
2DAGS
163SSS

Properties (8)

additional_info
630069031721201
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-03-17T23:49:37-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
10602