Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 30, 2021, 04:45 AM
  • 01 1186_01 1185_03292021_220448.mp4

Date
03/29/2021
W/O
886018
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00225
PipeID
P02040
Time
9:45 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8707
Sewer Name
01 WILCOX AVENUE TRUNK
City
BELL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_886018_TV01257_APR2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
21 in.
Upstream MH
01 1186
Downstream MH
01 1185
Dir. of Survey
Downstream
Length Surveyed
258.1 ft.
Total Length
258.1 ft.
Structural Index
3
Structural Quick
4D3J
Structural Rating
357
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
357
Pipe schematic from manhole 01 1186 to 01 1185
MH: 01 1186MH: 01 1185downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 11860 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK2.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start12.3 ft. SSS - Surface Spalling, from 08 to 10 o'clock, within 8 inches of joint: YES16.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start57.5 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: NO, 6"67.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"69 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"107.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"109.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"128 ft. FM - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES136.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start147.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES147.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"149.4 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: NO, 6"186.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"188.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"224.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"225 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES229 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"258.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish258.1 ft. AMH - Downstream Manhole, Survey Ends - 01 1185258.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish258.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (7)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 10 o'clock, within 8 inches of joint: YES

    12.3 ft. - Surface Spalling, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    16.7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

    128 ft. - Fracture Multiple, from 09 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    136.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    147.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    225 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (27)

DistanceCodeObservation
0MWM
258.1SSS
225SAP
149.4TFA
0MWL
224.9TFA
229TF
69TF
258.1AMH01 1185
57.5TF
188.5TF
0AMH01 1186
67.1TF
0MGOCONNECTION AT THE MH 3 OC'LOCK
12.3SSS
258.1FM
109.9TF
107.6TF
136.3FM
128FM
2.4SAV
147.6SAP
186.2TF
258.1SAV
16.7SSS
0MGOCONNECTION AT THE MH 9 OC'LOCK
147.6TF

Properties (7)

additional_info
630074032921201
custom_field_three
aggregate visible/ SURFACE SPALLING
custom_field_two
2
customer
1
datetime
2021-03-29T21:45:43-07:00
documentation
PROPIPE
is_lateral_inspection
false