Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 30, 2021, 04:32 AM
  • 01 1185_01 1184_03292021_222102.mp4

Date
03/29/2021
W/O
886018
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00225
PipeID
P02039
Time
9:32 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8707
Sewer Name
01 WILCOX AVENUE TRUNK
City
BELL
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_886018_TV01257_APR2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
21 in.
Upstream MH
01 1185
Downstream MH
01 1184
Dir. of Survey
Downstream
Length Surveyed
392.2 ft.
Total Length
392.2 ft.
Structural Index
3
Structural Quick
3O21
Structural Rating
236
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
236
Pipe schematic from manhole 01 1185 to 01 1184
MH: 01 1185MH: 01 1184downstream0 ft. AMH - Upstream Manhole, Survey Begins - 01 11850 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"9.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"50.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"53.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"91.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"94.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"126.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"128.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES130.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"171.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"199 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"210.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"213.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"226.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO253.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"278.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"291.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"324.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"331.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"333.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"392.2 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK392.2 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK392.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish392.2 ft. AMH - Downstream Manhole, Survey Ends - 01 1184

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

    128.8 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO

    226.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: NO

Observations (28)

DistanceCodeObservation
128.8SAP
333.9TF
0AMH01 1185
392.2MGOCONNECTION AT THE MH 9 OC'LOCK
5SAV
91.7TF
171.2TF
126.9TFA
50.7TF
6.6TF
392.2MGOCONNECTION AT THE MH 3 OC'LOCK
9.9TF
199TFA
0MWL
324.2TF
130.7TF
53.6TF
0MWM
331.4TF
278.7TF
392.2SAV
226.1SSS
94.6TF
253.5TF
291.2TF
392.2AMH01 1184
213.2TF
210.9TF

Properties (7)

additional_info
630074032921201
custom_field_three
aggregate visible/ SURFACE SPALLING
custom_field_two
3
customer
1
datetime
2021-03-29T21:32:29-07:00
documentation
PROPIPE
is_lateral_inspection
false