Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 13, 2021, 05:23 AM
  • 05 2367_05 2366_04122021_224140.mp4

Date
04/12/2021
W/O
887688
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00457
PipeID
P06098
Time
10:23 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8827
Sewer Name
05 IMPERIAL HIGHWAY EXTENSION TRUNK
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
09
Purpose
Routine Assessment
Project
CA_WO_887688
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 2366
Downstream MH
05 2367
Dir. of Survey
Upstream
Length Surveyed
319 ft.
Total Length
319 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2K00
O&M Rating
116
Overall Index
2
Overall Quick
Overall Rating
116
Pipe schematic from manhole 05 2366 to 05 2367
MH: 05 2366MH: 05 2367upstream0 ft. AMH - Upstream Manhole, Survey Ends - 05 23670.1 ft. MGO - General Observation - CONNECTION AT MH, 3 AND 9 O'CLOCK30.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish317 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start317 ft. DAZ - Deposits Attached Other, 5 %of cross sectional area, from 10 to 02 o'clock, , within 8 inches of joint: YES - deposits from 10-11 and 1-2319 ft. MWL - Water Level, 15 %of cross sectional area319 ft. AMH - Downstream Manhole, Survey Begins - 05 2366319 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK319 ft. MWM - Water Mark, 35 %of cross sectional area

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (9)

DistanceCodeObservation
319AMH05 2367
318.9MGOCONNECTION AT MH, 3 AND 9 O'CLOCK
0MWL
0AMH05 2366
2DAGS
288.7DAGS
0MGOCONNECTION AT MH, 3 O'CLOCK
2DAZdeposits from 10-11 and 1-2
0MWM

Properties (6)

custom_field_three
NO STRUCTURAL DEFECTS , GREASE
custom_field_two
4
customer
1
datetime
2021-04-12T22:23:40-07:00
documentation
PRO PIPE
is_lateral_inspection
false