Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 1, 2021, 06:17 AM
  • A 0571_A 0570_03312021_233901.mp4

Date
03/31/2021
W/O
886007
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00327
PipeID
P08352
Time
11:17 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8718
Sewer Name
A JOA-1A SOUTH HAWTHORNE-WARFIELD AV EXTENSION
City
LAWNDALE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
19
Purpose
Routine Assessment
Project
RFIR_WO_886007_TV05327_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
78 in.
Upstream MH
A 0571
Downstream MH
A 0570
Dir. of Survey
Downstream
Length Surveyed
516.5 ft.
Total Length
516.5 ft.
Structural Index
3
Structural Quick
4C3b
Structural Rating
604
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
604
Pipe schematic from manhole A 0571 to A 0570
MH: A 0571MH: A 0570downstream0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - A 05712 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start36 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"37.3 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start43.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"71.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"95.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"118.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"126.2 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish145.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start146.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"154.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"188.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"191.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"239.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"243.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"276.2 ft. MGO - General Observation - ABANDONED MH326.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6"340 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"362.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"391.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"409.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"442.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"450.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"494.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"497.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"514 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish514 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish516.4 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE516.5 ft. AMH - Downstream Manhole, Survey Ends - A 0570516.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    37.3 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    145.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - ABANDONED MH

    276.2 ft. - General Observation - ABANDONED MH

Observations (34)

DistanceCodeObservation
243.6TFC
516.5AMHA 0570
239.4TFC
118.3TFC
71.6TFC
191.2TFC
514SSS
2SSS
95.3TFC
36TFC
0MWL
0MWM
37.3FM
362.9TFC
409.5TFC
145.2CM
516.4MGOCONN @ MH 9 O'CLOCK/ACTIVE
450.9TF
43.8TFC
514CM
497.2TFC
188.3TFC
326.6TFC
340TFC
516.5CM
154.4TFC
126.2FM
2CM
0AMHA 0571
494.2TF
442.9TFC
391.1TFC
146.7TFC
276.2MGOABANDONED MH

Properties (7)

additional_info
630074033121203
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-03-31T23:17:52-07:00
documentation
PROPIPE
is_lateral_inspection
false