Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 9, 2021, 10:12 AM
  • 02 2382_02 1874_04092021_033536.mp4

Date
04/09/2021
W/O
873925
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00246
PipeID
P04233
Time
3:12 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8822
Sewer Name
02 DOUGLAS AVENUE TRUNK
City
E LOS ANGELES
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
12
Purpose
Routine Assessment
Project
CA_WO_873925
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
8 in.
Upstream MH
02 2382
Downstream MH
02 1874
Dir. of Survey
Downstream
Length Surveyed
269.4 ft.
Total Length
269.4 ft.
Structural Index
3
Structural Quick
3J2J
Structural Rating
268
O&M Index
2
O&M Quick
2J00
O&M Rating
106
Overall Index
2
Overall Quick
Overall Rating
374
Pipe schematic from manhole 02 2382 to 02 1874
MH: 02 2382MH: 02 1874downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 23820 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - STARTING AT MH 02 18750 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES71.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8" - OPEN88.5 ft. TF - Tap Factory Made, at 01 o'clock, -, within 8 inches of joint: YES, 8" - OPEN99.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8" - OPEN103.9 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8" - OPEN108.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8" - OPEN207.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8" - OPEN250.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8" - OPEN255.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 8" - OPEN267 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish267 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish268.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish269.4 ft. AMH - Downstream Manhole, Survey Ends - 02 1874269.4 ft. MGO - General Observation - MH 02 2382 DOES NOT EXIST

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    10.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8" - OPEN

    103.9 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8" - OPEN

Observations (22)

DistanceCodeObservation
255.4TFOPEN
0AMH02 2382
71.2TFOPEN
268.3CM
269.4AMH02 1874
207.5TFOPEN
2DAGS
2SSS
10.4CM
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
108.9TFOPEN
103.9TBOPEN
0MWM
0MGOSTARTING AT MH 02 1875
0MWL
269.4MGOMH 02 2382 DOES NOT EXIST
267DAGS
2CM
267SSS
99.3TFOPEN
88.5TFOPEN
250.3TFOPEN

Properties (6)

custom_field_three
MULTIPLE CRACKS, MH 02 2382 DOES NOT EXIST
custom_field_two
3
customer
1
datetime
2021-04-09T03:12:30-07:00
documentation
PRO PIPE
is_lateral_inspection
false