Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 1, 2021, 05:31 AM
  • 05 0947_05 0125_03312021_224357.mp4

Date
03/31/2021
W/O
886024
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00481
PipeID
P06179
Time
10:31 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8717
Sewer Name
05 MANCHESTER AVENUE PUMP TRUNK
City
HAWTHORNE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_886024_TV05335_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
15 in.
Upstream MH
05 0947
Downstream MH
05 0125
Dir. of Survey
Downstream
Length Surveyed
436.2 ft.
Total Length
436.2 ft.
Structural Index
3
Structural Quick
3P00
Structural Rating
258
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
258
Pipe schematic from manhole 05 0947 to 05 0125
MH: 05 0947MH: 05 0125downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 09470 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area4.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start31.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"77.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"129 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"177.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"230.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"279.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"328.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"379.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"436.2 ft. AMH - Downstream Manhole, Survey Ends - 05 0125436.2 ft. MGO - General Observation - ACTIVE CONNECTION AT THE MH 3 OC'LOCK436.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
0AMH05 0947
0MWL
4.6CM
436.2AMH05 0125
436.2MGOACTIVE CONNECTION AT THE MH 3 OC'LOCK
0MWM
279.3TFC
77.5TFC
177.7TFC
230.1TFC
129TFC
31.1TFC
379.9TFC
328.1TFC
436.2CM

Properties (7)

additional_info
630074033121202
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-03-31T22:31:11-07:00
documentation
PROPIPE
is_lateral_inspection
false