Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 3, 2021, 11:41 AM
  • 14 0101_14 0100A_03032021_045054.mp4

Date
03/03/2021
W/O
879965
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00577
PipeID
P25746
Time
3:41 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8588
Sewer Name
14 TRUNK "A"
City
LANCASTER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
18
Purpose
Routine Assessment
Project
WO_879965_TV14017_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
14 0100A
Downstream MH
14 0101
Dir. of Survey
Upstream
Length Surveyed
207 ft.
Total Length
207 ft.
Structural Index
2
Structural Quick
2G00
Structural Rating
82
O&M Index
2
O&M Quick
2G00
O&M Rating
82
Overall Index
2
Overall Quick
Overall Rating
164
Pipe schematic from manhole 14 0100A to 14 0101
MH: 14 0100AMH: 14 0101upstream0 ft. AMH - Upstream Manhole, Survey Ends - 14 01011.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish26.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"53.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"75.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"102.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"130.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"153 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"175.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"202.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"205 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start205 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start207 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE207 ft. MWM - Water Mark, 25 %of cross sectional area207 ft. MWL - Water Level, 20 %of cross sectional area207 ft. AMH - Downstream Manhole, Survey Begins - 14 0100A

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
207AMH14 0101
205.5DAGS
131.2TFC
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
2DAGS
153.6TFC
54TFC
4.8TFC
31.3TFC
0MWM
205SSS
180.8TFC
104.2TFC
2SSS
76.9TFC
0MWL
0AMH14 0100A

Properties (7)

additional_info
630069030221201
custom_field_three
LIGHT GREASE
custom_field_two
3
customer
1
datetime
2021-03-03T03:41:54-08:00
documentation
PRO PIPE
is_lateral_inspection
false