Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 3, 2021, 08:03 AM
  • 14 0103A_14 0103_03032021_010813.mp4

Date
03/03/2021
W/O
879965
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00577
PipeID
P18128
Time
12:03 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8588
Sewer Name
14 TRUNK "A"
City
LANCASTER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
18
Purpose
Routine Assessment
Project
WO_879965_TV14017_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
14 0103A
Downstream MH
14 0103
Dir. of Survey
Downstream
Length Surveyed
88.1 ft.
Total Length
88.1 ft.
Structural Index
2
Structural Quick
2B00
Structural Rating
34
O&M Index
2
O&M Quick
2B00
O&M Rating
34
Overall Index
2
Overall Quick
Overall Rating
68
Pipe schematic from manhole 14 0103A to 14 0103
MH: 14 0103AMH: 14 0103downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 0103A0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start14.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"38 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"62.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"81.4 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"85.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish86 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish88.1 ft. AMH - Downstream Manhole, Survey Ends - 14 0103

Observations (14)

DistanceCodeObservation
62.7TFC
85.8DAGS
81.4TBA
0AMH14 0103A
0MWL
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
0MWM
2DAGS
86SSS
0MGOROACHES @ MH
2SSS
88.1AMH14 0103
14.7TFC
38TFC

Properties (7)

additional_info
630069030221201
custom_field_three
LIGHT GREASE
custom_field_two
3
customer
1
datetime
2021-03-03T00:03:19-08:00
documentation
PRO PIPE
is_lateral_inspection
false