Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 3, 2021, 11:28 AM
  • 14 0100_14 0099A_03032021_043552.mp4

Date
03/03/2021
W/O
879965
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00577
PipeID
P18121
Time
3:28 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8588
Sewer Name
14 TRUNK "A"
City
LANCASTER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
18
Purpose
Routine Assessment
Project
WO_879965_TV14017_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
14 0099A
Downstream MH
14 0100
Dir. of Survey
Upstream
Length Surveyed
182.8 ft.
Total Length
182.8 ft.
Structural Index
2
Structural Quick
2F00
Structural Rating
72
O&M Index
2
O&M Quick
2F00
O&M Rating
72
Overall Index
2
Overall Quick
Overall Rating
144
Pipe schematic from manhole 14 0099A to 14 0100
MH: 14 0099AMH: 14 0100upstream0 ft. AMH - Upstream Manhole, Survey Ends - 14 01001.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish2.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish27.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"50.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"76.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"100.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"127.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"150 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"177 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"180.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start180.8 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start182.8 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE182.8 ft. MWM - Water Mark, 25 %of cross sectional area182.8 ft. MWL - Water Level, 15 %of cross sectional area182.8 ft. AMH - Downstream Manhole, Survey Begins - 14 0099A

Observations (16)

DistanceCodeObservation
181.3DAGS
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
5.8TFC
2DAGS
82.5TFC
155.6TFC
0MWM
0MWL
2SSS
182.8AMH14 0100
105.9TFC
132.4TFC
0AMH14 0099A
32.8TFC
55.6TFC
180SSS

Properties (7)

additional_info
630069030221201
custom_field_three
LIGHT GREASE
custom_field_two
3
customer
1
datetime
2021-03-03T03:28:55-08:00
documentation
PRO PIPE
is_lateral_inspection
false