Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 9, 2021, 05:07 AM
  • 18 0059_18 0058_04082021_222909.mp4

Date
04/08/2021
W/O
885861
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00689
PipeID
P13873
Time
10:07 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8725
Sewer Name
18 MILLS AVENUE TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_885861_TV18176_APR2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
18 0059
Downstream MH
18 0058
Dir. of Survey
Downstream
Length Surveyed
321.1 ft.
Total Length
321.1 ft.
Structural Index
3
Structural Quick
423L
Structural Rating
326
O&M Index
2
O&M Quick
2L00
O&M Rating
128
Overall Index
2
Overall Quick
Overall Rating
454
Pipe schematic from manhole 18 0059 to 18 0058
MH: 18 0059MH: 18 0058downstream0 ft. AMH - Upstream Manhole, Survey Begins - 18 00590 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/CAPPED0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 40% MAG COAT2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.7 ft. FM - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES29.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN114.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN115.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES120.3 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"141.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN205.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN211.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN232.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN277.6 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 4", 6" - OBJECT IN CONN/ACTIVE280.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6"304.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN319 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish319 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish321.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish321.1 ft. AMH - Downstream Manhole, Survey Ends - 05 0058

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    3.7 ft. - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    115.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (25)

DistanceCodeObservation
321.1SAV
0AMH18 0059
321.1AMH05 0058
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
304.9TFOPEN
0MGOCONN @ MH 9 O'CLOCK/CAPPED
2.2SAV
120.3TFA
232.5TFOPEN
0MWM
277.6TFDOBJECT IN CONN/ACTIVE
2DAGS
2MGO40% MAG COAT
0MWL
115.7FM
29.5TFOPEN
141.3TFOPEN
319DAGS
114.2TFOPEN
280.9TFA
2SSS
205.2TFOPEN
3.7FM
319SSS
211.1TFOPEN

Properties (7)

additional_info
630074040821201
custom_field_three
AGGREGATE VISIBLE/SOME FRACTURE'S
custom_field_two
3
customer
1
datetime
2021-04-08T22:07:03-07:00
documentation
PROPIPE
is_lateral_inspection
false