Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 9, 2021, 09:25 AM
  • 18 0040_18 0039_04092021_023449.mp4

Date
04/09/2021
W/O
885861
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00689
PipeID
P13855
Time
2:25 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8725
Sewer Name
18 MILLS AVENUE TRUNK
City
WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
21
Purpose
Routine Assessment
Project
RFIR_WO_885861_TV18176_APR2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0040
Downstream MH
18 0039
Dir. of Survey
Downstream
Length Surveyed
231.3 ft.
Total Length
231.3 ft.
Structural Index
3
Structural Quick
3H2H
Structural Rating
228
O&M Index
2
O&M Quick
2H00
O&M Rating
90
Overall Index
2
Overall Quick
Overall Rating
318
Pipe schematic from manhole 18 0040 to 18 0039
MH: 18 0040MH: 18 0039downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - ROACHES @ MH0 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 00402 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.4 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start21.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"73.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"82.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"139.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"146.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"191.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"198.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"229 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish229 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish231 ft. MGO - General Observation - ROACHES @ MH231.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish231.3 ft. AMH - Downstream Manhole, Survey Ends - 18 0039231.3 ft. MGO - General Observation - CONN @ MH 3 OC'LOCK/UNKNOWN

Observation photos (1)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.4 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (22)

DistanceCodeObservation
139.9TFC
73.6TFC
0MWM
0MGOROACHES @ MH
21.4TFC
198.3TFC
231.3SAV
231MGOROACHES @ MH
191.7TFC
231.3AMH18 0039
229DAGS
0MGOCONN @ MH 9 O'CLOCK/ACTIVE
146.3TFC
229SSS
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
2DAGS
0MWL
82.7TFC
2SSS
0AMH18 0040
2.4SAV
231.3MGOCONN @ MH 3 OC'LOCK/UNKNOWN

Properties (7)

additional_info
630074040821201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-04-09T02:25:28-07:00
documentation
PROPIPE
is_lateral_inspection
false