Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 12, 2021, 11:19 AM
  • 01 0423_01 0422_03122021_043713.mp4

Date
03/12/2021
W/O
880631
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00208
PipeID
P00905
Time
3:19 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8530
Sewer Name
01 HOLMES-WILLOWBROOK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
WO_880631_TV01030_MAR2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 0423
Downstream MH
01 0422
Dir. of Survey
Downstream
Length Surveyed
289.9 ft.
Total Length
289.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
0
Overall Quick
Overall Rating
0
Pipe schematic from manhole 01 0423 to 01 0422
MH: 01 0423MH: 01 0422downstream0 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE0 ft. MGO - General Observation - ROACHES @ MH0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 04230 ft. MWM - Water Mark, 20 %of cross sectional area2 ft. MGO - General Observation - 85% MAG COAT44.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"65.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"91.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"117.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"132.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"143.1 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"160.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"167.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"185.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"192.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN211.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"215.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"223.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6" - OPEN232.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6" - OPEN250.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"257.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"283.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"289.9 ft. MGO - General Observation - ROACHES @ MH289.9 ft. AMH - Downstream Manhole, Survey Ends - 01 0422289.9 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE

Observation photos (1)

  • General Observation - 85% MAG COAT

    2 ft. - General Observation - 85% MAG COAT

Observations (26)

DistanceCodeObservation
289.9MGOROACHES @ MH
283.7TFC
143.1TFA
250.8TFC
44.1TFC
160.5TFC
289.9AMH01 0422
0MGOCONN @ MH 3 O'CLOCK/ACTIVE
2MGO85% MAG COAT
215.7TFC
91.3TF
257.7TFC
65.9TFC
211.5TFC
0MGOROACHES @ MH
117.7TFA
289.9MGOCONN @ MH 3 O'CLOCK/ACTIVE
185.3TFC
132.4TF
223.8TFOPEN
0MWL
0AMH01 0423
0MWM
167.9TFC
192.9TFOPEN
232.7TFOPEN

Properties (7)

additional_info
630074031121203
custom_field_three
LIGHT GREASE
custom_field_two
3
customer
1
datetime
2021-03-12T03:19:15-08:00
documentation
PROPIPE
is_lateral_inspection
false