Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 15, 2021, 08:29 AM
  • 01 0420_01 0419A_03152021_013319.mp4

Date
03/15/2021
W/O
880631
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00208
PipeID
P00902
Time
1:29 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8599
Sewer Name
01 HOLMES-WILLOWBROOK TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
13
Purpose
Routine Assessment
Project
WO_880631_TV01030_MAR2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
01 0420
Downstream MH
01 0419A
Dir. of Survey
Downstream
Length Surveyed
25.3 ft.
Total Length
25.3 ft.
Structural Index
3
Structural Quick
3424
Structural Rating
20
O&M Index
2
O&M Quick
2400
O&M Rating
8
Overall Index
2
Overall Quick
Overall Rating
28
Pipe schematic from manhole 01 0420 to 01 0419A
MH: 01 0420MH: 01 0419Adownstream0 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 04200 ft. MGO - General Observation - CONN @ MH 3 O'CLOCK/ACTIVE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start15 ft. MGO - General Observation - MAG COAT23.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish23.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish23.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish25.3 ft. MGO - General Observation - CONN @ MH 9 O'CLOCK/ACTIVE25.3 ft. AMH - Downstream Manhole, Survey Ends - 01 0419A

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    15 ft. - General Observation - MAG COAT

Observations (13)

DistanceCodeObservation
0MWM
25.3MGOCONN @ MH 9 O'CLOCK/ACTIVE
23.3DAGS
23.3SSS
3.7SSS
15MGOMAG COAT
25.3AMH01 0419A
2DAGS
0MWL
3.7SAP
23.3SAP
0AMH01 0420
0MGOCONN @ MH 3 O'CLOCK/ACTIVE

Properties (7)

additional_info
630069031521001
custom_field_three
SPALLING/PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2021-03-15T01:29:19-07:00
documentation
PRO PIPE
is_lateral_inspection
false