Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 11, 2021, 11:10 AM
  • 32 1033_32 1032_03112021_042107.mp4

Date
03/11/2021
W/O
880299
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00841
PipeID
P19481
Time
3:10 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8598
Sewer Name
32 SOLEDAD CANYON TRUNK, SECTS 1,2,3,&4
City
SANTA CLARITA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 32
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_880299_TV32049_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
32 1033
Downstream MH
32 1032
Dir. of Survey
Downstream
Length Surveyed
350.2 ft.
Total Length
350.2 ft.
Structural Index
4
Structural Quick
4L00
Structural Rating
268
O&M Index
2
O&M Quick
2[00
O&M Rating
276
Overall Index
3
Overall Quick
Overall Rating
544
Pipe schematic from manhole 32 1033 to 32 1032
MH: 32 1033MH: 32 1032downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 32 10330 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - RUN LIST STATES NRCP.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Start11.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start348.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish348.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish348.1 ft. DAE - Deposits Attached Encrustation, 5 %of cross sectional area, from 09 to 03 o'clock, , within 8 inches of joint: YES, Finish350.2 ft. AMH - Downstream Manhole, Survey Ends - 32 1032

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MWM
2DAGS
0AMH32 1033
348.1FM
0MWL
11.6FM
0MGORUN LIST STATES NRCP.
2DAE
348.1DAGS
350.2AMH32 1032
348.1DAE

Properties (7)

additional_info
630069031021202
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2021-03-11T03:10:25-08:00
documentation
PRO PIPE
is_lateral_inspection
false