Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 12, 2021, 08:08 AM
  • 01 0541_01 0540_03122021_013535.mp4

Date
03/12/2021
W/O
880271
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00206
PipeID
P01029
Time
12:08 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8529
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_880271_TV01232_MAR2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
01 0541
Downstream MH
01 0540
Dir. of Survey
Downstream
Length Surveyed
322 ft.
Total Length
322 ft.
Structural Index
3
Structural Quick
3200
Structural Rating
6
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
6
Pipe schematic from manhole 01 0541 to 01 0540
MH: 01 0541MH: 01 0540downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 054132.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"33.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start73.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"76 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"124.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"167.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"170 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"193 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"253.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"273.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"303.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"307.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES316.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"319.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish322 ft. AMH - Downstream Manhole, Survey Ends - 01 0540

Observation photos (1)

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    307.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES

Observations (18)

DistanceCodeObservation
0MWL
316.2TF
73.3TF
193TF
170TF
167.1TF
76TFC
322AMH01 0540
0MWM
273.6TF
33.3SAV
32.4TFA
303.9TFA
124.2TF
307.2FL
0AMH01 0541
319.1SAV
253.7TFC

Properties (7)

additional_info
630074031121202
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-03-12T00:08:42-08:00
documentation
PRO PIPE
is_lateral_inspection