Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 12, 2021, 08:36 AM
  • 01 0540_01 0539_03122021_015043.mp4

Date
03/12/2021
W/O
880271
Weather
Dry
Operator/Surveyor
N.ZAHREDDINE
Sewer ID
Z00206
PipeID
P01028
Time
12:36 AM
Certificate
U-109-7948
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8529
Sewer Name
01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_880271_TV01232_MAR2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
01 0540
Downstream MH
01 0539
Dir. of Survey
Downstream
Length Surveyed
312.2 ft.
Total Length
312.2 ft.
Structural Index
3
Structural Quick
413K
Structural Rating
187
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
187
Pipe schematic from manhole 01 0540 to 01 0539
MH: 01 0540MH: 01 0539downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 01 05400 ft. MWL - Water Level, 10 %of cross sectional area2.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start70.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"78.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"88.2 ft. FM - Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES88.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"125.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"145.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"153.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"191.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"205.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"241 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"250.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"293.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"296.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"309.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish312.2 ft. AMH - Downstream Manhole, Survey Ends - 01 0539

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.3 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

    88.2 ft. - Fracture Multiple, from 08 to 10 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
0MWM
0AMH01 0540
153.2TFC
241TF
296.1TF
78.2TFC
88.3TFC
293.9TFC
312.2AMH01 0539
2.3SAV
309.3SAV
0MWL
88.2FM
191.2TF
70.7TF
205.9TF
125.7TFC
145.9TF
250.9TF

Properties (7)

additional_info
630074031121202
custom_field_three
Aggregate visable
custom_field_two
2
customer
1
datetime
2021-03-12T00:36:58-08:00
documentation
PRO PIPE
is_lateral_inspection
false