- Date
- 03/12/2021
- W/O
- 880271
- Weather
- Dry
- Operator/Surveyor
- N.ZAHREDDINE
- Sewer ID
- Z00206
- PipeID
- P01027
- Time
- 12:56 AM
- Certificate
- U-109-7948
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K8529
- Sewer Name
- 01 CROCKETT BOULEVARD-GLEN AVENUE TRUNK
- City
- LOS ANGELES
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 10
- Purpose
- Routine Assessment
- Project
- RFIR_WO_880271_TV01232_MAR2021
- Sewer Type
- Gravity
- Material
- NRCP
- Shape
- Circular
- Height
- 12 in.
- Width
- 15 in.
- Upstream MH
- 01 0539
- Downstream MH
- 01 0538A
- Dir. of Survey
- Downstream
- Length Surveyed
- 248.2 ft.
- Total Length
- 248.2 ft.
- Structural Index
- 3
- Structural Quick
- 433I
- Structural Rating
- 156
- O&M Index
- 1
- O&M Quick
- 1100
- O&M Rating
- 1
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 157
Pipe schematic from manhole 01 0539 to 01 0538A Observation photos (6)

3.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

3.7 ft. - Fracture Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

138.1 ft. - Repair Patch, from 09 to 12 o'clock, within 8 inches of joint: YES - RPR

185.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

185.6 ft. - Roots Fine Joint, from 09 to 12 o'clock, within 8 inches of joint: YES

239.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES