Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 24, 2021, 09:55 AM
  • 15 1107_15 1106_03242021_031707.mp4

Date
03/24/2021
W/O
885750
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00614
PipeID
P12867
Time
2:55 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8804
Sewer Name
15 MERCED TRUNK, SECTION 1
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
RFIR_WO_885750_TV15098_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
15 1107
Downstream MH
15 1106
Dir. of Survey
Downstream
Length Surveyed
351.7 ft.
Total Length
351.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
2
Overall Quick
Overall Rating
138
Pipe schematic from manhole 15 1107 to 15 1106
MH: 15 1107MH: 15 1106downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 11070 ft. MWL - Water Level, 10 %of cross sectional area2.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start17.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - DIRT75.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"99.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"159.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - DEBRIS223.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"332.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6"348.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish351.7 ft. AMH - Downstream Manhole, Survey Ends - 15 1106

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.1 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (12)

DistanceCodeObservation
75.1TF
17.6TFDIRT
159.4TFDEBRIS
99.1TF
2.1DAGS
0MWM
0AMH15 1107
0MWL
332.2TF
348.9DAGS
223.1TF
351.7AMH15 1106

Properties (6)

custom_field_three
GREASE/NO STRUCTURAL DEFECTS
custom_field_two
3
customer
1
datetime
2021-03-24T02:55:23-07:00
documentation
PRO PIPE
is_lateral_inspection
false