Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 25, 2021, 06:55 AM
  • 15 1104_15 1103_03252021_001227.mp4

Date
03/24/2021
W/O
885750
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00614
PipeID
P12864
Time
11:55 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8805
Sewer Name
15 MERCED TRUNK, SECTION 1
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
28
Purpose
Routine Assessment
Project
RFIR_WO_885750_TV15098_APR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
15 1104
Downstream MH
15 1103
Dir. of Survey
Downstream
Length Surveyed
319 ft.
Total Length
319 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
312L
O&M Rating
129
Overall Index
2
Overall Quick
Overall Rating
129
Pipe schematic from manhole 15 1104 to 15 1103
MH: 15 1104MH: 15 1103downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 11040 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 06 o'clock, , within 8 inches of joint: YES76.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"121.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"180.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"207.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - DEBRIS278.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"316.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish319 ft. AMH - Downstream Manhole, Survey Ends - 15 1103

Observation photos (2)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 15 %of cross sectional area, from 04 to 06 o'clock,  , within 8 inches of joint: YES

    2 ft. - Deposits Attached Grease, 15 %of cross sectional area, from 04 to 06 o'clock, , within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
0AMH15 1104
0MWM
316.5DAGS
207.7TFDEBRIS
121.8TF
2DAGS
0MWL
76.3TFC
319AMH15 1103
2DAGS
278.6TF
180.3TF
0MGOCONNECTION AT MH, 9 O'CLOCK

Properties (6)

custom_field_three
GREASE NO STRUCTURAL DEFECTS
custom_field_two
3
customer
1
datetime
2021-03-24T23:55:14-07:00
documentation
PRO PIPE
is_lateral_inspection
false