- Date
- 03/15/2021
- W/O
- 880095
- Weather
- Dry
- Operator/Surveyor
- M.MARTINEZ
- Sewer ID
- Z00699
- PipeID
- P14268
- Time
- 3:59 AM
- Certificate
- U-115-06022794
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K8636
- Sewer Name
- 18 SANTA FE STREET RELIEF TRUNK
- City
- WHITTIER
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 18
- Page No.
- 21
- Purpose
- Routine Assessment
- Project
- RFIR_WO_880095_TV18196_MAR2021
- Sewer Type
- Siphon
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 18 in.
- Width
- 18 in.
- Upstream MH
- 18 1101
- Downstream MH
- 18 1102
- Dir. of Survey
- Upstream
- Length Surveyed
- 11.8 ft.
- Total Length
- 11.8 ft.
- Structural Index
- 3
- Structural Quick
- 3100
- Structural Rating
- 3
- O&M Index
- 2
- O&M Quick
- 2200
- O&M Rating
- 4
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 7
Pipe schematic from manhole 18 1101 to 18 1102 Observation photos (4)

2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

8.8 ft. - Fracture Spiral, from 03 to 04 o'clock, within 8 inches of joint: YES

11.8 ft. - Deposits Attached Grease, 10 %of cross sectional area, from 01 to 11 o'clock, , within 8 inches of joint: YES

11.8 ft. - Survey Abandoned - VIEW OF U/S SIPHON FROM D/S MH