Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 25, 2021, 09:10 AM
  • 15 0896_15 0895_03252021_022647.mp4

Date
03/25/2021
W/O
885860
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00599
PipeID
P12690
Time
2:10 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8806
Sewer Name
15 CALIFORNIA AVENUE TRUNK
City
MONROVIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_885860_TV15182_APR2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0896
Downstream MH
15 0895
Dir. of Survey
Downstream
Length Surveyed
258.2 ft.
Total Length
258.2 ft.
Structural Index
4
Structural Quick
4I3I
Structural Rating
353
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
4
Overall Quick
Overall Rating
357
Pipe schematic from manhole 15 0896 to 15 0895
MH: 15 0896MH: 15 0895downstream0 ft. MGO - General Observation - CONNECTION AT MH, 3 AND 9 O'CLOCK0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 08960 ft. MWM - Water Mark, 35 %of cross sectional area2.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start4.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start65.4 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"149.1 ft. TBI - Tap Break-In Intruding, at 11 o'clock, -, -, within 8 inches of joint: YES, 8", 2"156.2 ft. TB - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"197.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"255.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish255.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish258.2 ft. AMH - Downstream Manhole, Survey Ends - 15 0895

Observation photos (6)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"

    65.4 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"

  • Tap Break-In Intruding, at 11 o'clock, -, -, within 8 inches of joint: YES, 8", 2"

    149.1 ft. - Tap Break-In Intruding, at 11 o'clock, -, -, within 8 inches of joint: YES, 8", 2"

  • Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"

    156.2 ft. - Tap Break-In, at 11 o'clock, -, within 8 inches of joint: YES, 8"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"

    197.5 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"

Observations (13)

DistanceCodeObservation
255.5SAP
258.2AMH15 0895
2.2SAP
0MGOCONNECTION AT MH, 3 AND 9 O'CLOCK
4.6FM
0MWL
0AMH15 0896
197.5TB
65.4TB
156.2TB
149.1TBI
255.5FM
0MWM

Properties (6)

custom_field_three
FRACTURES, AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2021-03-25T02:10:22-07:00
documentation
PRO PIPE
is_lateral_inspection
false