Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 25, 2021, 09:27 AM
  • 15 0895_15 0894_03252021_023635.mp4

Date
03/25/2021
W/O
885860
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00599
PipeID
P12689
Time
2:27 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8806
Sewer Name
15 CALIFORNIA AVENUE TRUNK
City
MONROVIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_885860_TV15182_APR2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0895
Downstream MH
15 0894
Dir. of Survey
Downstream
Length Surveyed
168.7 ft.
Total Length
168.7 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
99
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
99
Pipe schematic from manhole 15 0895 to 15 0894
MH: 15 0895MH: 15 0894downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 08952.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start61.5 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8" - DEBRIS113.1 ft. TB - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: YES, 8"166.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish168.7 ft. AMH - Downstream Manhole, Survey Ends - 15 0894

Observation photos (3)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8" - DEBRIS

    61.5 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8" - DEBRIS

  • Tap Break-In, at 03 o'clock, -, within 8 inches of joint: YES, 8"

    113.1 ft. - Tap Break-In, at 03 o'clock, -, within 8 inches of joint: YES, 8"

Observations (8)

DistanceCodeObservation
0MWM
113.1TB
168.7AMH15 0894
166.4SAP
0MWL
2.5SAP
0AMH15 0895
61.5TBDEBRIS

Properties (6)

custom_field_three
AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2021-03-25T02:27:51-07:00
documentation
PRO PIPE
is_lateral_inspection
false