Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 26, 2021, 06:39 AM
  • 15 0884_15 0883_03252021_235229.mp4

Date
03/25/2021
W/O
885860
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00599
PipeID
P12677
Time
11:39 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8807
Sewer Name
15 CALIFORNIA AVENUE TRUNK
City
MONROVIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_885860_TV15182_APR2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0884
Downstream MH
15 0883
Dir. of Survey
Downstream
Length Surveyed
311.7 ft.
Total Length
311.7 ft.
Structural Index
3
Structural Quick
3K2K
Structural Rating
305
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
305
Pipe schematic from manhole 15 0884 to 15 0883
MH: 15 0884MH: 15 0883downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 08840 ft. MWM - Water Mark, 35 %of cross sectional area2.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.6 ft. MGO - General Observation - MAG COAT2.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start6.8 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 8"66.2 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8" - TOP HAT309.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish309.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish311.7 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK311.7 ft. AMH - Downstream Manhole, Survey Ends - 15 0883

Observation photos (5)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - MAG COAT

    2.6 ft. - General Observation - MAG COAT

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 8"

    6.8 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 8"

  • Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8" - TOP HAT

    66.2 ft. - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8" - TOP HAT

Observations (12)

DistanceCodeObservation
66.2TFTOP HAT
0MWL
2.6SAP
311.7MGOCONNECTION AT MH, 3 O'CLOCK
6.8TBA
2.6MGOMAG COAT
0AMH15 0884
311.7AMH15 0883
309.2SSS
309.2SAP
0MWM
2.6SSS

Properties (6)

custom_field_three
AGGREGATE PROJECTING, SPALLING
custom_field_two
3
customer
1
datetime
2021-03-25T23:39:20-07:00
documentation
PRO PIPE
is_lateral_inspection
false