Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 26, 2021, 09:39 AM
  • 15 0878_15 0877_03262021_030136.mp4

Date
03/26/2021
W/O
885860
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00599
PipeID
P12671
Time
2:39 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8807
Sewer Name
15 CALIFORNIA AVENUE TRUNK
City
MONROVIA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
05
Purpose
Routine Assessment
Project
RFIR_WO_885860_TV15182_APR2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
15 0877
Downstream MH
15 0878
Dir. of Survey
Upstream
Length Surveyed
444.3 ft.
Total Length
444.3 ft.
Structural Index
3
Structural Quick
3Q2Q
Structural Rating
440
O&M Index
3
O&M Quick
3200
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
446
Pipe schematic from manhole 15 0877 to 15 0878
MH: 15 0877MH: 15 0878upstream0 ft. AMH - Upstream Manhole, Survey Ends - 15 08780.2 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK0.2 ft. MGO - General Observation - CONNECTION AT MH, 2 O'CLOCK CAPPED1.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish252.3 ft. RMJ - Roots Medium Joint, from 03 to 04 o'clock, 15 %, within 8 inches of joint: YESR354.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"428.6 ft. RML - Roots Medium Lateral, from 03 to 04 o'clock, 15 %, within 8 inches of joint: YES428.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"442.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start442.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start442.3 ft. MGO - General Observation - MAG COAT444.3 ft. AMH - Downstream Manhole, Survey Begins - 15 0877444.3 ft. MWM - Water Mark, 35 %of cross sectional area444.3 ft. MGO - General Observation - CONNECTION AT MH, 3 O'CLOCK444.3 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (6)

  • General Observation - MAG COAT

    2 ft. - General Observation - MAG COAT

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Lateral, from 03 to 04 o'clock, 15 %, within 8 inches of joint: YES

    15.7 ft. - Roots Medium Lateral, from 03 to 04 o'clock, 15 %, within 8 inches of joint: YES

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"

    15.7 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: YES, 8"

  • Roots Medium Joint, from 03 to 04 o'clock, 15 %, within 8 inches of joint: YESR

    192 ft. - Roots Medium Joint, from 03 to 04 o'clock, 15 %, within 8 inches of joint: YESR

Observations (16)

DistanceCodeObservation
444.3AMH15 0878
0AMH15 0877
2.1SAP
89.8TFC
0MWM
0MGOCONNECTION AT MH, 3 O'CLOCK
444.1MGOCONNECTION AT MH, 3 O'CLOCK
192RMJ
15.7RML
442.9SAP
2MGOMAG COAT
2.1SSS
15.7TB
0MWL
442.9SSS
444.1MGOCONNECTION AT MH, 2 O'CLOCK CAPPED

Properties (6)

custom_field_three
SPALLING, AGGREGATE PROJECTING
custom_field_two
3
customer
1
datetime
2021-03-26T02:39:56-07:00
documentation
PRO PIPE
is_lateral_inspection
false