- Date
- 02/17/2021
- W/O
- 875034
- Weather
- Dry
- Operator/Surveyor
- M.MARTINEZ
- Sewer ID
- Z00780
- PipeID
- P16224
- Time
- 2:42 AM
- Certificate
- U-115-06022794
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K8606
- Sewer Name
- 21 POMONA BOULEVARD INTERCEPTOR TRUNK
- City
- POMONA
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 21
- Page No.
- 14
- Purpose
- Routine Assessment
- Project
- WO_875034_TV21019_FEB2021
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 33 in.
- Width
- 33 in.
- Upstream MH
- 21 1130
- Downstream MH
- 21 1129
- Dir. of Survey
- Downstream
- Length Surveyed
- 267.3 ft.
- Total Length
- 267.3 ft.
- Structural Index
- 3
- Structural Quick
- 3J2J
- Structural Rating
- 265
- O&M Index
- 4
- O&M Quick
- 4F00
- O&M Rating
- 140
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 405
Pipe schematic from manhole 21 1130 to 21 1129 Observation photos (5)

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - General Observation - MAG COAT

2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2 ft. - Alignment Left, 30 %, Start

197 ft. - Alignment Left, 30 %, Start