Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 12, 2021, 10:28 AM
  • 15 0192_15 0191_03122021_035108.mp4

Date
03/12/2021
W/O
880319
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00620
PipeID
P12114
Time
2:28 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8634
Sewer Name
15 PECK ROAD TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
17
Purpose
Routine Assessment
Project
WO_880319_TV15022_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0192
Downstream MH
15 0191
Dir. of Survey
Downstream
Length Surveyed
359.9 ft.
Total Length
359.9 ft.
Structural Index
3
Structural Quick
3L21
Structural Rating
194
O&M Index
2
O&M Quick
2M00
O&M Rating
142
Overall Index
2
Overall Quick
Overall Rating
336
Pipe schematic from manhole 15 0192 to 15 0191
MH: 15 0192MH: 15 0191downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 01920 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start15.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES30.8 ft. CS - Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES39.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES47.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start69.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"130.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"155 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"268.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"297.9 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: YES, 8"346.4 ft. TF - Tap Factory Made, at 11 o'clock, -, within 8 inches of joint: YES, 8"356.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish356.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish359.9 ft. AMH - Downstream Manhole, Survey Ends - 15 0191

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    15.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES

    30.8 ft. - Crack Spiral, from 12 to 01 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    39.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    47.3 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (18)

DistanceCodeObservation
39.2CM
346.4TF
0MWM
297.9TFC
30.8CS
0AMH15 0192
130.5TFA
155TF
356.8CM
359.9AMH15 0191
47.3CM
0MWL
69.3TFC
15.3CM
268.8TF
2DAGS
356.8DAGS
0MGOCONNECTION AT MH, 9 O'CLOCK

Properties (6)

custom_field_three
multiple cracks
custom_field_two
3
customer
1
datetime
2021-03-12T02:28:59-08:00
documentation
PRO PIPE
is_lateral_inspection
false