Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 11, 2021, 07:24 AM
  • 15 0209_15 0208_03112021_004301.mp4

Date
03/10/2021
W/O
880319
Weather
Light Rain
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00620
PipeID
P12131
Time
11:24 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8633
Sewer Name
15 PECK ROAD TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
17
Purpose
Routine Assessment
Project
WO_880319_TV15022_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0209
Downstream MH
15 0208
Dir. of Survey
Downstream
Length Surveyed
271.5 ft.
Total Length
271.5 ft.
Structural Index
3
Structural Quick
3321
Structural Rating
11
O&M Index
2
O&M Quick
2J00
O&M Rating
106
Overall Index
2
Overall Quick
Overall Rating
117
Pipe schematic from manhole 15 0209 to 15 0208
MH: 15 0209MH: 15 0208downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 15 02092.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start16.6 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES74.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES102.7 ft. CS - Crack Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES104.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"145.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"191.5 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"237.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"252.6 ft. CM - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES268.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish271.5 ft. AMH - Downstream Manhole, Survey Ends - 15 0208

Observation photos (5)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    16.6 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    74.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES

    102.7 ft. - Crack Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

    252.6 ft. - Crack Multiple, from 12 to 04 o'clock, within 8 inches of joint: YES

Observations (15)

DistanceCodeObservation
145.2TFC
252.6CM
237.4TFC
271.5AMH15 0208
0MWM
74.1CM
0MWL
104.1TFC
16.6CM
191.5TFC
0MGOCONNECTION AT MH, 9 O'CLOCK
102.7CS
268.3DAGS
2.2DAGS
0AMH15 0209

Properties (6)

custom_field_three
CRACKS
custom_field_two
4
customer
1
datetime
2021-03-10T23:24:08-08:00
documentation
PRO PIPE
is_lateral_inspection
false