Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 11, 2021, 08:14 AM
  • 15 0208_15 0207_03112021_012547.mp4

Date
03/11/2021
W/O
880319
Weather
Damp
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00620
PipeID
P12130
Time
12:14 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8633
Sewer Name
15 PECK ROAD TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
17
Purpose
Routine Assessment
Project
WO_880319_TV15022_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0208
Downstream MH
15 0207
Dir. of Survey
Downstream
Length Surveyed
232.1 ft.
Total Length
232.1 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2F00
O&M Rating
68
Overall Index
2
Overall Quick
Overall Rating
71
Pipe schematic from manhole 15 0208 to 15 0207
MH: 15 0208MH: 15 0207downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 020829.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"56.8 ft. CM - Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES60.2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start95 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"144.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"228.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish232.1 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK232.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0207

Observation photos (2)

  • Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

    56.8 ft. - Crack Multiple, from 11 to 04 o'clock, within 8 inches of joint: YES

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    60.2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
144.4TFC
29.6TFC
95TFC
232.1MGOCONNECTION AT MH, 9 O'CLOCK
228.8DAGS
232.1AMH15 0207
0MWM
0MWL
60.2DAGS
56.8CM
0AMH15 0208

Properties (6)

custom_field_three
CRACKS
custom_field_two
4
customer
1
datetime
2021-03-11T00:14:53-08:00
documentation
PRO PIPE
is_lateral_inspection
false