Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 11, 2021, 10:30 AM
  • 15 0200_15 0199_03112021_034152.mp4

Date
03/11/2021
W/O
880319
Weather
Heavy Rain
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00620
PipeID
P12122
Time
2:30 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8633
Sewer Name
15 PECK ROAD TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
17
Purpose
Routine Assessment
Project
WO_880319_TV15022_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0200
Downstream MH
15 0199
Dir. of Survey
Downstream
Length Surveyed
239.7 ft.
Total Length
239.7 ft.
Structural Index
2
Structural Quick
3122
Structural Rating
7
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
2
Overall Quick
Overall Rating
8
Pipe schematic from manhole 15 0200 to 15 0199
MH: 15 0200MH: 15 0199downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 02000 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area15.7 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES66.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"100.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 10"107.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"132.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 8"159.5 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES188.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES208.4 ft. CL - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES239.7 ft. MGO - General Observation - CONNECTION AT MH, 9 O'CLOCK239.7 ft. AMH - Downstream Manhole, Survey Ends - 15 0199

Observation photos (5)

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

    15.7 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 10"

    100.7 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: YES, 10"

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    159.5 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    188.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

    208.4 ft. - Crack Longitudinal, at 08 o'clock, within 8 inches of joint: YES

Observations (13)

DistanceCodeObservation
239.7MGOCONNECTION AT MH, 9 O'CLOCK
208.4CL
0AMH15 0200
15.7RFJ
0MWL
132.3TFC
100.7TB
0MWM
66.8TF
159.5CL
239.7AMH15 0199
188.1CM
107.6TFC

Properties (6)

custom_field_three
CRACKS
custom_field_two
4
customer
1
datetime
2021-03-11T02:30:07-08:00
documentation
PRO PIPE
is_lateral_inspection
false