Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 12, 2021, 08:37 AM
  • 15 0194_15 0193_03122021_020243.mp4

Date
03/12/2021
W/O
880319
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00620
PipeID
P12116
Time
12:37 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8634
Sewer Name
15 PECK ROAD TRUNK
City
EL MONTE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
17
Purpose
Routine Assessment
Project
WO_880319_TV15022_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
15 0194
Downstream MH
15 0193
Dir. of Survey
Downstream
Length Surveyed
350.8 ft.
Total Length
350.8 ft.
Structural Index
3
Structural Quick
3I22
Structural Rating
148
O&M Index
2
O&M Quick
312M
O&M Rating
142
Overall Index
2
Overall Quick
Overall Rating
290
Pipe schematic from manhole 15 0194 to 15 0193
MH: 15 0194MH: 15 0193downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 01940 ft. MWM - Water Mark, 35 %of cross sectional area2.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start15.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES77.3 ft. CS - Crack Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES98.3 ft. CS - Crack Spiral, from 08 to 09 o'clock, within 8 inches of joint: YES114.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start115.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"132.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"194 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"246.8 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 8"246.8 ft. RMC - Roots Medium Connection, at 12 o'clock, 15 %, within 8 inches of joint: YES254.3 ft. RFJ - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES272.1 ft. TBA - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 8"321.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 8"345.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: YES, 8"348.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish348.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish350.8 ft. AMH - Downstream Manhole, Survey Ends - 15 0193

Observation photos (9)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    15.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES

    77.3 ft. - Crack Spiral, from 09 to 11 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 08 to 09 o'clock, within 8 inches of joint: YES

    98.3 ft. - Crack Spiral, from 08 to 09 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    114.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 8"

    246.8 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 8"

  • Roots Medium Connection, at 12 o'clock, 15 %, within 8 inches of joint: YES

    246.8 ft. - Roots Medium Connection, at 12 o'clock, 15 %, within 8 inches of joint: YES

  • Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

    254.3 ft. - Roots Fine Joint, at 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 8"

    272.1 ft. - Tap Break-In Active, at 11 o'clock, -, within 8 inches of joint: YES, 8"

Observations (20)

DistanceCodeObservation
0MWL
114.5CM
272.1TBA
194TF
348.7CM
345.8TFA
254.3RFJ
115.8TF
350.8AMH15 0193
132.1TF
246.8TBA
246.8RMC
77.3CS
348.7DAGS
0AMH15 0194
2.3DAGS
321.3TF
15.7CM
98.3CS
0MWM

Properties (6)

custom_field_three
multiple cracks
custom_field_two
3
customer
1
datetime
2021-03-12T00:37:04-08:00
documentation
PRO PIPE
is_lateral_inspection
false