Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 15, 2021, 08:53 AM
  • 18 0378_18 0377_03152021_020727.mp4

Date
03/15/2021
W/O
880270
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00690
PipeID
P14212
Time
1:53 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8635
Sewer Name
18 NORTH NORWALK TRUNK
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
25
Purpose
Routine Assessment
Project
RFIR_WO_880270_TV18095_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0378
Downstream MH
18 0377
Dir. of Survey
Downstream
Length Surveyed
354.7 ft.
Total Length
354.7 ft.
Structural Index
4
Structural Quick
4200
Structural Rating
8
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
8
Pipe schematic from manhole 18 0378 to 18 0377
MH: 18 0378MH: 18 0377downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 03784.9 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES8.1 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start109.5 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"220.7 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"334.2 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"352.4 ft. FM - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Finish354.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0377354.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK

Observation photos (2)

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

    4.9 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

    8.1 ft. - Fracture Multiple, from 07 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
8.1FM
0MWL
334.2TF
4.9FM
0MWM
354.7AMH18 0377
352.4FM
354.7MGOCONNECTION AT MH 9 O'CLOCK
0AMH18 0378
220.7TFC
109.5TFC

Properties (6)

custom_field_three
FRACTURES
custom_field_two
3
customer
1
datetime
2021-03-15T01:53:57-07:00
documentation
PRO PIPE
is_lateral_inspection
false