Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 15, 2021, 09:41 AM
  • 18 0374_18 0373_03152021_025412.mp4

Date
03/15/2021
W/O
880270
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00690
PipeID
P14208
Time
2:41 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8635
Sewer Name
18 NORTH NORWALK TRUNK
City
NORWALK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
25
Purpose
Routine Assessment
Project
RFIR_WO_880270_TV18095_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
18 0374
Downstream MH
18 0373
Dir. of Survey
Downstream
Length Surveyed
326.7 ft.
Total Length
326.7 ft.
Structural Index
4
Structural Quick
4100
Structural Rating
4
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
4
Pipe schematic from manhole 18 0374 to 18 0373
MH: 18 0374MH: 18 0373downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 03740 ft. MGO - General Observation - CONNECTION AT MH 3 & 9 O'CLOCK CAPPED0 ft. MWM - Water Mark, 35 %of cross sectional area3.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start92.1 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"207 ft. TFC - Tap Factory Made Capped, at 12 o'clock, -, within 8 inches of joint: YES, 8"318.2 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: YES, 8"324.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish326.7 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK326.7 ft. AMH - Downstream Manhole, Survey Ends - 18 0373

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
0MWL
0AMH18 0374
0MGOCONNECTION AT MH 3 & 9 O'CLOCK CAPPED
318.2TFA
324.3FM
92.1TF
0MWM
326.7MGOCONNECTION AT MH 9 O'CLOCK
207TFC
3.7FM
326.7AMH18 0373

Properties (6)

custom_field_three
FRACTURES
custom_field_two
3
customer
1
datetime
2021-03-15T02:41:33-07:00
documentation
PRO PIPE
is_lateral_inspection
false