Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 17, 2021, 07:24 AM
  • 18 0919_18 0399_03172021_004419.mp4

Date
03/17/2021
W/O
880300
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00699
PipeID
P14233
Time
12:24 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K8639
Sewer Name
18 SANTA FE STREET RELIEF TRUNK
City
S. WHITTIER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 18
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_880300_TV18173_MAR2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
18 0919
Downstream MH
18 0399
Dir. of Survey
Downstream
Length Surveyed
331 ft.
Total Length
331 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
3
O&M Quick
3200
O&M Rating
6
Overall Index
3
Overall Quick
Overall Rating
11
Pipe schematic from manhole 18 0919 to 18 0399
MH: 18 0919MH: 18 0399downstream0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 18 09199 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"10.2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start10.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start89.4 ft. RML - Roots Medium Lateral, from 04 to 08 o'clock, 10 %, within 8 inches of joint: YES89.4 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"90.4 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"90.5 ft. RML - Roots Medium Lateral, from 04 to 08 o'clock, 30 %, within 8 inches of joint: YES151 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 8"189.9 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"191.5 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"202.3 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 8"298.2 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 8"329.4 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish329.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish331 ft. AMH - Downstream Manhole, Survey Ends - 18 0399

Observation photos (11)

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"

    9 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    10.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Lateral, from 04 to 08 o'clock, 10 %, within 8 inches of joint: YES

    89.4 ft. - Roots Medium Lateral, from 04 to 08 o'clock, 10 %, within 8 inches of joint: YES

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"

    89.4 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"

    90.4 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"

  • Roots Medium Lateral, from 04 to 08 o'clock, 30 %, within 8 inches of joint: YES

    90.5 ft. - Roots Medium Lateral, from 04 to 08 o'clock, 30 %, within 8 inches of joint: YES

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"

    189.9 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"

    191.5 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: YES, 8"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 8"

    202.3 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 8"

  • Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 8"

    298.2 ft. - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: YES, 8"

Observations (18)

DistanceCodeObservation
90.5RML
90.4TB
0MWM
151TF
329.4SSS
191.5TB
331AMH18 0399
0MWL
10.2SAP
298.2TB
329.4SAP
89.4RML
9TB
189.9TB
202.3TB
0AMH18 0919
10.2SSS
89.4TB

Properties (6)

custom_field_three
AGGREGATE PROJECTING,SPALLING
custom_field_two
2
customer
1
datetime
2021-03-17T00:24:35-07:00
documentation
PRO PIPE
is_lateral_inspection
false