Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 3, 2021, 06:34 AM
  • 05 1733_05 1732_03022021_234745.mp4

Date
03/02/2021
W/O
880429
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00471
PipeID
P06960
Time
10:34 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8493
Sewer Name
05 LOMITA TRUNK
City
TORRANCE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
32
Purpose
Routine Assessment
Project
WO_880429_TV05130_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
18 in.
Upstream MH
05 1733
Downstream MH
05 1732
Dir. of Survey
Downstream
Length Surveyed
388.9 ft.
Total Length
388.9 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2N00
O&M Rating
152
Overall Index
2
Overall Quick
Overall Rating
152
Pipe schematic from manhole 05 1733 to 05 1732
MH: 05 1733MH: 05 1732downstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 17333 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start385 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish388.9 ft. AMH - Downstream Manhole, Survey Ends - 05 1732

Observations (6)

DistanceCodeObservation
385DAGS
3DAGS
388.9AMH05 1732
0MWL
0MWM
0AMH05 1733

Properties (7)

additional_info
630074030221201
custom_field_three
NO SEVERE DEFECTS
custom_field_two
4
customer
1
datetime
2021-03-02T22:34:26-08:00
documentation
PROPIPE
is_lateral_inspection
false