Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Apr 13, 2021, 07:51 AM
  • 16 0515_16 0514_4132021_010105.mp4

Date
04/13/2021
W/O
0884081
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00659
PipeID
P13566
Time
12:51 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1775R
Sewer Name
16 LAMANDA PARK TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
18
Purpose
Maintenance Related
Project
20210413MDM_LAMANDA_PARK_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
24 in.
Upstream MH
16 0515
Downstream MH
16 0514
Dir. of Survey
Downstream
Length Surveyed
279.8 ft.
Total Length
279.8 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
1
O&M Quick
1500
O&M Rating
5
Overall Index
1
Overall Quick
Overall Rating
5
Pipe schematic from manhole 16 0515 to 16 0514
MH: 16 0515MH: 16 0514downstream0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 12:55AM143.5 ft. RFC - Roots Fine Connection, from 09 to 12 o'clock, within 8 inches of joint: YES - 4%158.4 ft. RFC - Roots Fine Connection, from 09 to 12 o'clock, within 8 inches of joint: YES - 1%203.3 ft. RFC - Roots Fine Connection, from 10 to 01 o'clock, within 8 inches of joint: YES - 3%224.3 ft. RFC - Roots Fine Connection, from 12 to 01 o'clock, within 8 inches of joint: YES - 1%264.1 ft. RFJ - Roots Fine Joint, from 07 to 10 o'clock, within 8 inches of joint: YESR - 4%279.8 ft. AMH - Downstream Manhole, Survey Ends - 1:15AM

Observations (10)

DistanceCodeObservation
143.5RFC4%
158.4RFC1%
224.3RFC1%
0MGOConn. @ Mh, 3 O' Clock. Active
279.8AMH1:15AM
0MWL
0MWM
0AMH12:55AM
203.3RFC3%
264.1RFJ4%

Properties (5)

additional_info
POST ROOT EVALUATION
customer
LACSD
datetime
2021-04-13T00:51:50-07:00
documentation
MARTIN,OLIVER 111,BARR
is_lateral_inspection
false