Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 9, 2021, 09:55 AM
  • 05 2231_05 0775_03092021_030312.mp4

Date
03/09/2021
W/O
880266
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00553
PipeID
P06003
Time
1:55 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8497
Sewer Name
05 MANCHESTER-VERMONT DIVERSION EXTENSION TRUNK
City
LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 01
Page No.
09
Purpose
Routine Assessment
Project
WO_880266_TV05272_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 0775
Downstream MH
05 2231
Dir. of Survey
Upstream
Length Surveyed
211.7 ft.
Total Length
211.7 ft.
Structural Index
4
Structural Quick
4G00
Structural Rating
164
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
164
Pipe schematic from manhole 05 0775 to 05 2231
MH: 05 0775MH: 05 2231upstream0 ft. AMH - Upstream Manhole, Survey Ends - 05 22310 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0.1 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish207.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start211.7 ft. AMH - Downstream Manhole, Survey Begins - 05 0775211.7 ft. MWM - Water Mark, 20 %of cross sectional area211.7 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    4.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
211.7AMH05 2231
4.4FM
211.7MGOCONNECTION AT THE MH 9 OC'LOCK
0AMH05 0775
211.7MGOCONNECTION AT THE MH 3 OC'LOCK
0MWM
0MWL
211.6FM

Properties (7)

additional_info
630074030821202
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-03-09T01:55:45-08:00
documentation
PROPIPE
is_lateral_inspection
false