Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 8, 2021, 09:22 AM
  • 05 0641_05 0640_02082021_014034.mp4

Date
02/08/2021
W/O
870427
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00520
PipeID
P05866
Time
1:22 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8468
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK
City
INGLEWOOD
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_870427_TV05343_JAN2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
21 in.
Width
10 in.
Upstream MH
05 0641
Downstream MH
05 0640
Dir. of Survey
Downstream
Length Surveyed
257 ft.
Total Length
257 ft.
Structural Index
3
Structural Quick
3E22
Structural Rating
91
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
91
Pipe schematic from manhole 05 0641 to 05 0640
MH: 05 0641MH: 05 0640downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 06410 ft. MWM - Water Mark, 25 %of cross sectional area2 ft. MGO - General Observation - GREASE THROUGHOUT LINE7.5 ft. TB - Tap Break-In, at 12 o'clock, -, within 8 inches of joint: NO, 6"13.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"16.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"20.1 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start30.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish30.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start56 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"58.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"104.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"107.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"165.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"167.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"172.9 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish228.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"231.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"255.9 ft. MGO - General Observation - DROP CONN. @ MH 9 O'CLOCK255.9 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK CAPPED255.9 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK CAPPED257 ft. AMH - Downstream Manhole, Survey Ends - 05 0640

Observation photos (2)

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    20.1 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    30.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

Observations (23)

DistanceCodeObservation
30.2CL
255.9MGODROP CONN. @ MH 9 O'CLOCK
104.4TFC
30.2FL
228.1TFC
107.6TFC
56TFC
0MWL
231.6TFC
255.9MGOCONNECTION AT THE MH 3 OC'LOCK CAPPED
20.1CL
0AMH05 0641
165.1TFC
7.5TB
2MGOGREASE THROUGHOUT LINE
58.9TFC
172.9FL
16.9TFC
13.5TFC
167.6TFC
255.9MGOCONNECTION AT THE MH 9 OC'LOCK CAPPED
257AMH05 0640
0MWM

Properties (7)

additional_info
630074020821001
custom_field_three
FRACTURE'S
custom_field_two
3
customer
1
datetime
2021-02-08T01:22:25-08:00
documentation
PROPIPE
is_lateral_inspection
false