Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 3, 2021, 11:28 AM
  • 05 1835_05 1834_03032021_045602.mp4

Date
03/03/2021
W/O
880386
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00492
PipeID
P07057
Time
3:28 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8494
Sewer Name
05 NARBONNE AVENUE CONNECTION TRUNK
City
LOMITA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
36
Purpose
Routine Assessment
Project
WO_880386_TV05375_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
05 1835
Downstream MH
05 1834
Dir. of Survey
Downstream
Length Surveyed
201.4 ft.
Total Length
201.4 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
99
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
99
Pipe schematic from manhole 05 1835 to 05 1834
MH: 05 1835MH: 05 1834downstream-0.1 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - 05 18350 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area18.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES39.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start57 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"64.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"74.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"83.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"96.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"101.7 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"120.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"162.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"168.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"201 ft. MGO - General Observation - POSSIBLE SURFACE SPALLING THROUGHOUT THE REACH, 9 TO 3 OCLOCK201.3 ft. AMH - Downstream Manhole, Survey Ends - 05 1834201.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    18.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    39.5 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

    101.7 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

Observations (18)

DistanceCodeObservation
201.3AMH05 1834
0AMH05 1835
120.1TFC
18.6CM
201MGOPOSSIBLE SURFACE SPALLING THROUGHOUT THE REACH, 9 TO 3 OCLOCK
101.7TB
162.2TF
-0.1MGOCONNECTION AT THE MH 3 OC'LOCK
57TF
39.5CM
64.2TFC
168.1TF
201.3CM
0MWL
83.9TF
74.8TFC
96.2TF
0MWM

Properties (7)

additional_info
630074030221202
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-03-03T03:28:49-08:00
documentation
PROPIPE
is_lateral_inspection
false