Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Mar 10, 2021, 05:42 AM
  • 05 1094_05 1093_03092021_225618.mp4

Date
03/09/2021
W/O
880269
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00488
PipeID
P06328
Time
9:42 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8498
Sewer Name
05 MONETA EXTENSION TRUNK, SECTION 1
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_880269_TV05328_MAR2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
15 in.
Upstream MH
05 1094
Downstream MH
05 1093
Dir. of Survey
Downstream
Length Surveyed
317.4 ft.
Total Length
317.4 ft.
Structural Index
3
Structural Quick
423L
Structural Rating
332
O&M Index
2
O&M Quick
2L00
O&M Rating
126
Overall Index
2
Overall Quick
Overall Rating
458
Pipe schematic from manhole 05 1094 to 05 1093
MH: 05 1094MH: 05 1093downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 10940 ft. MWL - Water Level, 55 %of cross sectional area0 ft. MWM - Water Mark, 60 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start3.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start22.9 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"109.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES122.5 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6" - OPEN127.6 ft. FS - Fracture Spiral, from 06 to 11 o'clock, within 8 inches of joint: YES211.7 ft. FS - Fracture Spiral, from 09 to 04 o'clock, within 8 inches of joint: YES222.4 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: NO, 6"226.5 ft. FS - Fracture Spiral, from 08 to 12 o'clock, within 8 inches of joint: YES305.7 ft. FM - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES315 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish315 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish317 ft. MGO - General Observation - ROACHES @ MH317.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish317.4 ft. AMH - Downstream Manhole, Survey Ends - 05 1093

Observation photos (6)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    109.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 06 to 11 o'clock, within 8 inches of joint: YES

    127.6 ft. - Fracture Spiral, from 06 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 09 to 04 o'clock, within 8 inches of joint: YES

    211.7 ft. - Fracture Spiral, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 08 to 12 o'clock, within 8 inches of joint: YES

    226.5 ft. - Fracture Spiral, from 08 to 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    305.7 ft. - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

Observations (19)

DistanceCodeObservation
305.7FM
317MGOROACHES @ MH
226.5FS
2SSS
3.8CM
127.6FS
2DAGS
211.7FS
222.4TF
317.4CM
317.4AMH05 1093
0AMH05 1094
109.7FM
0MWL
315DAGS
122.5TFOPEN
315SSS
0MWM
22.9TFA

Properties (7)

additional_info
630074030921201
custom_field_three
MULTIPLE FRACTURES
custom_field_two
2
customer
1
datetime
2021-03-09T21:42:35-08:00
documentation
PROPIPE
is_lateral_inspection
false