- Date
- 03/05/2021
- W/O
- 875111
- Weather
- Dry
- Operator/Surveyor
- J. BUENROSTRO
- Sewer ID
- Z00323
- PipeID
- P08148
- Time
- 9:28 AM
- Certificate
- U-715-07000770
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- K8653
- Sewer Name
- A JOA-1A LOS COYOTES WRP INTERCEPTOR
- City
- SOUTH GATE
- Loc. details
- Easement/Right of Way
- Location Code
- D
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 26
- Purpose
- V
- Project
- RFIR_WO_875111_TV30023_FEB2021
- Sewer Type
- Siphon
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 75 in.
- Width
- 42 in.
- Upstream MH
- A 0211
- Downstream MH
- A 1288
- Dir. of Survey
- Upstream
- Length Surveyed
- 250.4 ft.
- Total Length
- 250.4 ft.
- Structural Index
- 3
- Structural Quick
- 3I2I
- Structural Rating
- 245
- O&M Index
- 2
- O&M Quick
- 412K
- O&M Rating
- 122
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 367
Pipe schematic from manhole A 0211 to A 1288 Observation photos (3)

4.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

4.7 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

200.4 ft. - Deposits Settled Other, 10 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: NO, Start - SLUDGE