Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Feb 24, 2021, 06:55 AM
  • A 0193_A 0192_02232021_230223.mp4

Date
02/23/2021
W/O
875111
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00323
PipeID
P08127
Time
10:55 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K8488
Sewer Name
A JOA-1A LOS COYOTES WRP INTERCEPTOR
City
SOUTH GATE
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
29
Purpose
Routine Assessment
Project
RFIR_WO_875111_TV30023_FEB2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
78 in.
Width
42 in.
Upstream MH
A 0192
Downstream MH
A 0193
Dir. of Survey
Upstream
Length Surveyed
2.1 ft.
Total Length
2.1 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
3
O&M Quick
3100
O&M Rating
3
Overall Index
3
Overall Quick
Overall Rating
8
Pipe schematic from manhole A 0192 to A 0193
MH: A 0192MH: A 0193upstream0 ft. DSZ - Deposits Settled Other, 20 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: NO - SLUDGE0 ft. MGO - General Observation - 60% MAG COAT0 ft. MSA - Survey Abandoned - CAM BLKD BY SLUDGE 20%0 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES0.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES2.1 ft. MWM - Water Mark, 15 %of cross sectional area2.1 ft. AMH - Upstream Manhole, Survey Begins - A 01922.1 ft. MWL - Water Level, 10 %of cross sectional area

Observation photos (3)

  • Deposits Settled Other,  20 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: NO - SLUDGE

    2.1 ft. - Deposits Settled Other, 20 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: NO - SLUDGE

  • Survey Abandoned - CAM BLKD BY SLUDGE 20%

    2.1 ft. - Survey Abandoned - CAM BLKD BY SLUDGE 20%

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

    2.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
0MWM
0AMHA 0192
2.1DSZSLUDGE
2.1MGO60% MAG COAT
2.1MSACAM BLKD BY SLUDGE 20%
2SSS
0MWL
2.1SAV

Properties (7)

additional_info
630074022321201
custom_field_two
5
customer
1
datetime
2021-02-23T22:55:18-08:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
27983